PKTMJ-90

PKTMJ-90

Fire damper resistant against seismic events

PKTMJ-90 - Fire damper resistant against seismic events, effects of high pressure and higher air flow velocity.

Properties

Min. dimensions 200 x 200 x 375 mm; max. dimensions 1600 x 1000 x 375 mm, round Ø180 - 1000 mm
CE certified acc. to EN 15650
Tested in accordance with EN 1366-2
Classified acc. to EN 13501-3+A1
Fire resistance up to EIS 90
External Casig leakage class C, Internal leakage class 2 acc. to EN 1751
Corrosion resistant acc. to EN 15650
Cycling test in class C10 000 acc. to EN 15650
Damper actuating mechanical, electrical, or electromechanical
Plain bearings - maintenance-free design resistant to high-level seismic stresses
Max. airflow 15 m/s
Max. pressure difference 2500 Pa (inner pressure / external pressure - dynamic pressure)
Seismic resistant
Guaranteed service life 40 years
Suitable for explosion - risk environments, Zone 1 and Zone 2

Specifications

Fire damper resistant against seismic events, effects of high pressure and higher air flow velocity.